BROOKNES
SUPPLIES AND SERVICE LIMITED.
TAMESIDE BUS. DEV. CTR., WINDMILL LANE, DENTON,
MANCHESTER. M34 3QS
TEL. - 0161 336 3971
FAX. - 0161 335 0106 EMAIL. - sales@brooknes.co.uk
EQUIPMENT: 50V DC. combined battery/charger
tripping supply unit.
UNIT REFERENCE:
TSU5012M-2.
HOUSING: Wall
mounting, welded fabrication, steel enclosure with hinged door and un-drilled
gland plates.
Dimensions: 480mm high
x 480mm wide x 150mm deep.
Finish: Silicon
grey to RAL7032.
Weight: 16Kg.
BATTERIES: Sealed nickel cadmium type, having a
long maintenance-free life.
Capacity: 1.4Ah.
Number of cells: 40.
Max. peak discharge for 0.3sec to 0.65V/cell: 80A.
INPUT: 220-250V AC. 50/60Hz.
Single phase. Full load: 55VA.
OUTPUT: Nominal voltage: 50V DC.
Maximum voltage: 57.5V DC.
Minimum voltage: 42.0V DC.
Tripping
(pulse) output.
Maximum current: 40A for
0.1sec.
Standing load
(continuous) output.
Maximum current: 0.5A.
Available capacity: 0.75Ah.
ACCESSORIES: Mains input MCB.
Mains pilot
lamp.
Dummy load test
pushbutton.
Battery/output
voltmeter.
PROTECTION: Mains input: Double pole, thermal MCB - 5A.
Charger output: Single
pole, fuse - 20mm 1A.
Rectifier input: Single
pole, fuse - 20mm 6.3A.
Tripping output: None.
Standing load output: Single pole,
fuse - NIT 6.
TERMINALS: Mains input: SAK 2.5.
Tripping output: STL 5.
Standing load output: SAK 6N.
Alarms output: SAK 2.5.
ALARMS: Standard: Charge failed. ) Each
with either;
Optional: Mains
failed. ) 2 x c/o contacts, or,
(May Low
voltage. ) 1 x c/o contact (or
affect High voltage. ) o/p to com. alarm) +
cubicle Earth fault. ) local pilot lamp.
Size). Common alarm. -
with 2 x c/o contacts.
REVIEWED: D.G. Sims DATE: 14/12/1998 ISSUE: 03
AUTHORISED: . DATE: . PAGE: 1/1