BROOKNES SUPPLIES AND SERVICE LIMITED.

 

TAMESIDE BUS. DEV. CTR., WINDMILL LANE, DENTON, MANCHESTER. M34 3QS

 

TEL. - 0161 336 3971  FAX. - 0161 335 0106  EMAIL. - sales@brooknes.co.uk

 

 

EQUIPMENT:                30V DC. combined battery/charger tripping supply unit.

 

UNIT REFERENCE:       TSU3012-1.

 

HOUSING:                    Wall mounting, welded fabrication, steel enclosure with hinged door and un-drilled gland plates.

Dimensions:                  480mm high x 240mm wide x 150mm deep.

Finish:                          Silicon grey to RAL7032.

Weight:                         12Kg.

 

BATTERIES:                 Sealed nickel cadmium type, having a long maintenance-free life.

Capacity:                      1.4Ah.

Number of cells:            25.

Max. peak discharge for 0.3sec to 0.65V/cell:      80A.

 

INPUT:                          220-250V AC.  50/60Hz.  Single phase.  Full load:           5VA.

 

OUTPUT:                      Nominal voltage:            30V DC.

Maximum voltage:          35.5V DC.

Minimum voltage:           26.25V DC.

 

Tripping (pulse) output.

Maximum current:          40A for 0.1sec.

 

Standing load (continuous) output.

Maximum current:          None.

Available capacity:         None.

 

ACCESSORIES:           Mains input MCB.

Mains pilot lamp.

Dummy load test pushbutton.

Battery/output voltmeter.

 

PROTECTION:              Mains input:                  Double pole, thermal MCB - 5A.

Charger output:             Single pole, fuse - 20mm 1A.

Rectifier input:               None.

Tripping output:             None.

Standing load output:     None.

 

TERMINALS:                 Mains input:                  SAK 2.5.

Tripping output:             STL 5.

Standing load output:     None.

Alarms output:               SAK 2.5.

 

ALARMS:                      Standard:                      Charge failed.               - with    2 x c/o contacts.

Optional:                       Mains failed.                  )           Cannot be

                                    Low voltage.                  )           accommodated

                                    High voltage.                 )           in this

                                    Earth fault.                    )           size of

                                    Common alarm.             )           enclosure.

 

Return to home page.

 

REVIEWED:     D.G. Sims                                 DATE:  14/12/1998                                ISSUE: 03

 

AUTHORISED:  .                                               DATE:  .                                               PAGE:  1/1