EQUIPMENT: 50V
DC. combined battery/charger tripping/closing supply unit.
UNIT REFERENCE: CSU50100M-6.
HOUSING: Wall mounting, welded fabrication,
steel enclosure with hinged door and un-drilled gland plates.
Dimensions: 720mm high x 480mm wide x 150mm
deep.
Finish: Silicon grey to RAL7032.
Weight: 54Kg.
BATTERIES: Sealed
nickel cadmium type, having a long maintenance-free life.
Capacity: 10.0Ah.
Number of cells: 42.
Max. peak discharge for
0.3sec to 0.65V/cell: 200A.
INPUT: 220-250V
AC. 50/60Hz. Single phase. Full load: 220VA.
OUTPUT: Nominal
voltage: 50V DC.
Maximum voltage, trip: 60.2V DC. close: 59.7V DC.
Minimum voltage, trip: 42.0V DC. close: 45.0V DC.
Tripping (pulse) output.
Maximum current: 100A for 0.1sec.
Closing (pulse) output.
Maximum current: 93A for 0.15sec.
Standing load (continuous) output.
Maximum current: 2.0A.
Available capacity: 3.0Ah.
ACCESSORIES: Mains
input MCB.
Mains pilot lamp.
Dummy load test pushbutton.
Battery/output voltmeter.
PROTECTION: Mains
input: Double pole, thermal
MCB - 5A.
Charger output: Single pole, fuse - 20mm 1A.
Rectifier input: Single pole, fuse - 20mm 6.3A.
Tripping output: None.
Closing output: Double pole, fuse - TIS 40.
Standing load output: Single pole, fuse - NIT 6.
TERMINALS: Mains
input: SAK 2.5.
Tripping output: STL 5.
Closing output: SAK 35.
Standing load output: SAK 6N.
Alarms output: SAK 2.5.
ALARMS: Standard: Charge failed. ) Each with either;
Optional: Mains failed. ) 2
x c/o contacts, or,
(May Low voltage. ) 1 x c/o contact (or
affect High
voltage. ) o/p to com. alarm) +
cubicle Earth
fault. ) local pilot lamp.
Size). Common
alarm. - with 2 x c/o contacts.
REVIEWED: D.G. Sims DATE: 14/12/1998 ISSUE: 03