BRIEF SPECIFICATIONS OF STANDARD CLOSING/TRIPPING SUPPLY UNITS

 

TYPE

VOLTS

TRIP LOAD

CLOSE LOAD

STANDING LOAD / CAPACITY

CUBICLE SIZE

WEIGHT

 

 

 

 

 

 

 

CSU3070-1

30V

100A

63A

None / None

M

23Kg

CSU3070M-2

30V

100A

63A

1.0A / 1.0Ah

L

39Kg

CSU30100M-3

30V

125A

63A

3.0A / 3.0Ah

L

43Kg

CSU30100-4

30V

150A

144A

None / None

L

38Kg

CSU30100M-5

30V

150A

144A

1.0A / 1.0Ah

L

44Kg

 

 

 

 

 

 

 

CSU5040-1

50V

70A

40A

None / None

L

32Kg

CSU5040M-2

50V

70A

40A

1.0A / 1.0Ah

L

40Kg

CSU5070M-3

50V

70A

40A

2.0A / 3.0Ah

L

43Kg

CSU5070-4

50V

100A

93A

None / None

L

37Kg

CSU5070M-5

50V

100A

93A

1.0A / 1.0Ah

L

45Kg

CSU50100M-6

50V

100A

93A

2.0A / 3.0Ah

L

54Kg

 

 

 

 

 

 

 

CSU11020-1

110V

40A

20A

None / None

L

34Kg

CSU11040-4

110V

70A

40A

None / None

L

42Kg

CSU11040M-5

110V

70A

40A

1.0A / 1.0Ah

L

50Kg

CSU11070M-6

110V

70A

40A

1.0A / 3.0Ah

L

59Kg

 

NOTES.

 

Loads          The tripping loads detailed above are for up to 0.1 seconds duration.
The closing loads detailed above are for up to 0.15 seconds duration.
The units are capable of up to the maximum standing loads detailed above both continuously and after mains failure, with up to the shown capacity available on discharge.

 

Cubicle         Dimensions (in mm)

M – 480H x 480W x 150D

L – 720H x 480W x 150D

The standard paint finish is Silicon Grey to RAL7032.

 

Alarms         Charge fail is fitted as standard, the additional optional alarms that are available are:- DC. low voltage, DC. high voltage, mains failure, earth leakage and common alarm.  Each alarm is available with either 2 x changeover contacts, or 1 x changeover contact (or output to common alarm) plus local pilot lamp.  To accommodate one or all of the alarms in some units may necessitate an increase in the size of the cubicle.

 

 

 

 

 

 

 

 

To go to detailed specifications for all the standard units listed above, just click the unit type.

 

Return to home page.